Reference Manual
00809-0100-4811, Rev DA
Section 4: Basic Configuration/Start-Up
January 2015
Basic Configuration/Start-Up
Table 4-2. Measurement Mode
Interface Immersed Probe is used for applications where the probe is fully immersed in liquid. In
this mode, the transmitter ignores the upper product level. See Interface measurements with
fully immersed probes on page 99 for more information.
Note
Only use Interface Immersed Probe for applications where interface is measured for a fully
immersed probe.
4.4.9 Probe angle
Enter the angle between the probe and the vertical line. The default value is equal to zero. Do
not change this value if the transmitter is mounted with the probe along the vertical line (which
is normally the case).
4.4.10 Maximum upper product thickness
For interface measurements, the Maximum Upper Product Thickness parameter can be used in
special cases when the dielectric constant of the upper product is relatively high. By setting this
parameter, you can avoid that interface measurements get out of range.
4.4.11 Damping
The default damping value is 10. Normally, this value does not need to be changed. The
Damping parameter determines how quickly the transmitter responds to level changes and how
robust the measurement signal is against noise. See High level rates on page 98 for more
information.
4.4.12 Display panel
Select which variables to be displayed and the desired language to be used. The display toggles
between the selected variables every two seconds.
Model Measurement mode
3301 Level
(1)
, Interface Immersed probe
(1) Default setting.
3302 Level, Level and Interface
(1)
, Interface Immersed probe
HART Comm
1, 3, 2, 4
HART Comm
1, 4, 5, 2
HART Comm
1, 3, 5
HART Comm
1, 4, 2