Reference Manual
00809-0100-4811, Rev DA
Section 6: Service and Troubleshooting
January 2015
Service and Troubleshooting
6.3.8 Changing the probe
Note
See the safety information on page 93 before changing the probe.
1. Loosen the nut.
2. Remove the transmitter head from the old probe.
3. On the new probe, make sure the protection plug is removed and the upper surface of
the process seal is clean. Also make sure that the spring-loaded pin at the center of the
process seal is properly inserted.
4. Mount the transmitter head on the new probe.
5. Fasten the nut again.
6. If the new probe is not of the same type as the old one, update the transmitter
configuration by setting the probe type parameter to the appropriate value:
HART Fast Key sequence [1, 3, 2, 3],
or
RCT Setup/Probe.
7. Measure the probe length and enter the measured value:
HART Fast Key sequence [1, 3, 2, 2],
or
RCT Setup/Probe.
8. Verify that the transmitter is calibrated.
Note
Flexible and rigid probes require different radar electronics and cannot be used with the same
transmitter head.
Nut
P
r
o
b
e
Transm itter
head
Process seal