Section 4: Basic Configuration/Start-Up
January 2015
Basic Configuration/Start-Up
Strapping table
Use a strapping table if a standard tank type does not provide sufficient accuracy. Use most of
the strapping points in regions where the tank shape is non-linear. A maximum of 10 points can
be added to the strapping table.
Figure 4-3. Strapping Points
Actual tank bottom may look like this.
Using only 3 strapping points results in a level-to-volume profile that is
more angular than the actual shape.
Using 6 of the points at the bottom of the tank yields a level-to-volume
profile that is similar to the actual tank bottom.