Appendix C: Rosemount 3300 Series with HART
®
to Modbus
®
Converter
January 2015
Rosemount 3300 Series with HART
®
to Modbus
®
Converter
C.8.1 Using RCT to change communication parameters
Note
To change Modbus communication parameters, the Rosemount 3300 Series Transmitter must
use HART address 1, the default address.
Note
After changing communication parameters, disconnect the HART modem and wait at least 60
seconds for the change to take effect.
In case the MA (+)/MB (-) terminals are used for connection to the HMC, disconnect the RS-485
Converter, cycle power to the transmitter and wait up to 60 seconds for the change to take
effect.
To change the Modbus address and communication parameters
(1)
in Rosemount Radar
Configuration Tools (RCT):
1. Start RCT and connect to the transmitter.
2. In the RCT workspace Project Bar, select the Setup icon to open the Setup window.
3. Select the Output tab.
4. Select the Modbus Setup button.
(1) The Modbus Setup function is available in RCT version 2.03.0002 and later.
Modbus Setup