Appendix C: Rosemount 3300 Series with HART
®
to Modbus
®
Converter
January 2015
Rosemount 3300 Series with HART
®
to Modbus
®
Converter
Table C-18. Parameter Values (in case of Emerson Process Management ROC800 Series)
The Input Register Base Number needs to be added to the Input Register address of the
Rosemount 3300 Series Transmitter. In this case, register 1300 needs to have 1300 entered as
the address.
C.11.2 Emerson Process Management FloBoss 107
Figure C-9. Wiring Diagram for Connecting 3300 Modbus to Emerson Process
Management FloBoss 107
Table C-19. Parameter Values (in case of Emerson Process Management FloBoss 107)
The Input Register Base Number needs to be added to the Input Register address of the
Rosemount 3300 Series Transmitter. In this case, register 1300 needs to have 1300 entered as
the address.
Parameter Value
Baud Rate 9600
Floating Point Format Code 0
RTU Data Type Conversion Code 66
Input Register Base Number 0
Parameter Value
Baud Rate 9600
Floating Point Format Code 0
RTU Data Type Conversion Code 66
Input Register Base Number 0
RS-485
A
B
NC
NC
PWR
GND
MA (+)
MB (-)
PWR +
PWR -
FloBoss 107
3300 Modbus
Power Supply
+ 8 to + 30 Vdc
(max. rating)
GND