Service and Troubleshooting
6.2 Advanced configuration
This section covers non-standard configuration.
6.2.1 User defined upper reference point
If you want to specify your own upper reference point, you can do this by setting the Calibration
Offset parameter.
Figure 6-1. Tank Geometry
To set the desired upper reference point, do the following:
1. Adjust the reference gauge height to the distance from the tank bottom to the desired
upper reference point.
2. Add the distance between the upper reference point and the transmitter reference
point to the calibration offset value that is stored in the transmitter database.
With the HART Communicator, Calibration Offset is available as HART Fast Key
sequence [1, 4, 5, 5].
In Radar Configuration Tool (RCT), Calibration Offset is available under the Tools
section in the RCT Project Bar:
Device Commands > Basics > Set Calibration Offset.
Reference gauge
height
Product level
Upper reference point
Transmitter
reference point
Calibration
offset