182
Reference Manual
00809-0100-4811, Rev DA
Appendix C: Rosemount 3300 Series with HART
®
to Modbus
®
Converter
January 2015
Rosemount 3300 Series with HART
®
to Modbus
®
Converter
Figure C-3. Connection Terminals for Rosemount 3300 with HART to Modbus Converter
C.5.2 RS-485 bus
The Rosemount 3300 Series Transmitter does not provide electrical isolation between
the RS-485 bus and the transmitter power supply.
Maintain a bus topology and minimize stub length.
Figure C-4 identifies multidrop wiring topology, where up to 32 devices may be wired
on one RS-485 bus.
The RS-485 bus needs to be terminated once at each end, but should not be terminated
elsewhere on the bus.
C.5.3 Installation cases
Install the Rosemount 3300 Series Transmitters as shown in Figure C-4.
Use common ground for Modbus Master and power supply.
The Power cables and RS-485 Bus are in the same cable installation.
A ground cable is installed and shall be used (cable size > 4 mm according to
IEC60079-14, or size according to applicable national regulations and standards). A
properly installed threaded conduit connection may provide sufficient ground.
The cable shielding is grounded at master site (optional).
Note
The HMC equipped transmitter contains intrinsically safe circuits that require the housing to be
grounded in accordance with national and local electrical codes. Failure to do so may impair the
protection provided by the equipment.
HART + HART -