34
Reference Manual
00809-0100-4811, Rev DA
Section 3: Installation
January 2015
Installation
Rigid twin lead
The spacers are put closer together at the probe end. The maximum amount that can be cut
away is related to the ordering length L.
To cut a Rigid Twin Lead probe, do the following:
1. Cut the rods to the desired length:
You may cut up to 19.7 in.
(500 mm) from the probe end for
probe length (L) above 46.5 in.
(1180 mm).
For probe length
20.5 to 46.5 in. (520 to
1180 mm) the minimium length
is 20.5 in. (520 mm).
For probe length 15.7 to 20.5 in.
(400 to 520 mm) the minimium
length is 15.7 in. (400 mm).
2. Update the transmitter configuration
to the new probe length, see “Probe
length” on page 70.
Max. shortening length:
19.7 in. / 500 mm
L > 46.5 in. (1180 mm)
L
20.5 in. < L < 46.5 in.
Minimum probe length
20.5 in. / 520 mm
L
(520 mm < L < 1180 mm)
Minimum probe length
15.7 in. / 400 mm
L
15.7 in. < L < 20.5 in.
(400 mm < L < 520 mm)
Vista de página 43
1 2 ... 39 40 41 42 43 44 45 46 47 48 49 ... 223 224